全空(kong)氣(qi)系(xi)統中(zhong),送入各個區(或(huo)房間)的(de)空(kong)氣(qi)在機房內集中(zhong)處(chu)理。對(dui)空(kong)氣(qi)進行處(chu)理的(de)設備稱為空(kong)氣(qi)處(chu)理機組,或(huo)稱空(kong)調機組。
空(kong)氣(qi)處理機組(zu)(Air handling unit,AHU):空(kong)氣(qi)處理機組(zu)(AHU)是(shi)一種(zhong)(zhong)集中(zhong)式空(kong)氣(qi)處理系(xi)(xi)統,它起(qi)源于設(she)備集中(zhong)設(she)置,通過風(feng)(feng)管分(fen)配加熱(re)空(kong)氣(qi)的(de)強(qiang)制式熱(re)風(feng)(feng)采暖(nuan)和通風(feng)(feng)系(xi)(xi)統。基本的(de)集中(zhong)式系(xi)(xi)統是(shi)一種(zhong)(zhong)全空(kong)氣(qi)單區(qu)域系(xi)(xi)統,一般包括風(feng)(feng)機、加熱(re)器(qi)、冷(leng)卻器(qi)以及過濾器(qi)各組(zu)件。這里所說(shuo)的(de)AHU,指的(de)是(shi)一次回風(feng)(feng)系(xi)(xi)統,其基本工作(zuo)過程是(shi):室(shi)外(wai)來的(de)新風(feng)(feng)與(yu)室(shi)內的(de)一部分(fen)回風(feng)(feng)混(hun)合后,經過濾器(qi)濾掉空(kong)氣(qi)中(zhong)的(de)粉塵、煙塵、黑(hei)煙和有機粒(li)子等有害物(wu)質。
干凈的(de)(de)空(kong)(kong)氣經(jing)風機送(song)到冷卻器(qi)或加(jia)熱器(qi)進行冷卻或加(jia)熱,以達到使人感到舒適、適宜的(de)(de)程度,然后(hou)送(song)入房間(jian)。空(kong)(kong)氣調節(jie)過程根據冬、夏季節(jie)的(de)(de)變化,典型的(de)(de)集(ji)中式空(kong)(kong)氣處理系統調節(jie)過程也不相同(tong)。
用(yong)(yong)于調(diao)(diao)節室內空氣(qi)溫濕度和潔凈度的(de)設備。有滿足熱濕處理(li)要求用(yong)(yong)的(de)空氣(qi)加熱器、空氣(qi)冷卻器、空氣(qi)加濕器,凈化空氣(qi)用(yong)(yong)的(de)空氣(qi)過濾器,調(diao)(diao)節新(xin)風(feng)、回(hui)風(feng)用(yong)(yong)的(de)混風(feng)箱以(yi)及降低(di)通(tong)風(feng)機(ji)噪聲用(yong)(yong)的(de)消聲器。空氣(qi)處理(li)機(ji)組(zu)均設有通(tong)風(feng)機(ji)。根據全年空氣(qi)調(diao)(diao)節的(de)要求,機(ji)組(zu)可配置與冷熱源(yuan)相連接(jie)的(de)自動調(diao)(diao)節系統。
新風(feng)機組(zu)主(zhu)要針對室外新風(feng)的(de)狀態點進(jin)行(xing)處理(li),而空(kong)氣(qi)處理(li)機組(zu)主(zhu)要針對室內(nei)循環風(feng)的(de)狀態進(jin)行(xing)處理(li)。與(yu)風(feng)機盤管(guan)加新風(feng)系(xi)統及單元式空(kong)調器相比,它具有(you)處理(li)風(feng)量大、空(kong)氣(qi)品質高、節能等優點,尤其適合商場、展覽館、機場等大空(kong)間(jian)、大人流量的(de)系(xi)統。
一(yi)個(ge)好的空氣處理機(ji)組應該(gai)具(ju)有占用空間少、功能多(duo)、噪(zao)音(yin)低、能耗(hao)低、造型美觀、安裝(zhuang)維修(xiu)方便等特點。但是由于其(qi)功能段(duan)多(duo)、結構(gou)復(fu)雜,要做到顧(gu)此而(er)不失彼,全(quan)面兼顧(gu),就要求(qiu)設計人員和建設單位在(zai)材(cai)質、制造工藝(yi)、結構(gou)特性、選(xuan)型計算時多(duo)方比較,方能取得較為滿(man)意(yi)的效果。
性(xing)能特征概述
1 保溫性能
空氣(qi)處(chu)(chu)理(li)(li)機(ji)(ji)組壁板(ban)(ban)一般采用(yong)(yong)雙層彩色鋼(gang)板(ban)(ban)或冷軋鋼(gang)板(ban)(ban)粉(fen)末噴(pen)涂(底板(ban)(ban)內(nei)側板(ban)(ban)有的采用(yong)(yong)不銹鋼(gang)制成),中間(jian)的保溫(wen)(wen)材(cai)料多為聚氨酯發泡或阻燃性(xing)離心玻璃(li)棉。如果(guo)單從導熱(re)系數、吸水性(xing)和密度來看,二(er)者均是較好的保溫(wen)(wen)材(cai)料。但由于空氣(qi)處(chu)(chu)理(li)(li)機(ji)(ji)組在運行過程中,送、回風機(ji)(ji)高速運轉,箱(xiang)體振(zhen)動(dong)比較大(da)(da),而玻璃(li)棉的質(zhi)量輕(qing),結構(gou)中有較大(da)(da)間(jian)隙容(rong)易因長期振(zhen)動(dong)而出現脫(tuo)落,導致導熱(re)系數急劇增大(da)(da),失去保溫(wen)(wen)作用(yong)(yong),從而造成空氣(qi)處(chu)(chu)理(li)(li)機(ji)(ji)組壁板(ban)(ban)結露,使送風溫(wen)(wen)度偏(pian)高。
但是并(bing)非采用(yong)聚氨酯發泡就(jiu)一(yi)定(ding)具有好(hao)的保溫效果,如劣(lie)質(zhi)的聚氨酯發泡保溫材(cai)料(liao)也會影(ying)響使用(yong)效果。故(gu)在選擇(ze)空氣處理機(ji)組時,不能輕率選擇(ze)壁(bi)板保溫材(cai)料(liao)。
2 漏風率
大(da)多(duo)數空(kong)氣(qi)處(chu)(chu)理機組(zu)(zu)(zu)廠家(jia)的(de)(de)箱(xiang)體結構都是(shi)由面板與(yu)鋁合金框(kuang)架或角鋼焊接框(kuang)架組(zu)(zu)(zu)合而成。箱(xiang)體密(mi)封處(chu)(chu)理也是(shi)選型(xing)時(shi)應引起高度重視的(de)(de)一個方面,因為(wei)如果(guo)漏風(feng)(feng)(feng)率過(guo)大(da)會產生兩種(zhong)后果(guo):一種(zhong)是(shi)由于漏風(feng)(feng)(feng)過(guo)多(duo)導致送(song)(song)風(feng)(feng)(feng)量不足(zu);另一種(zhong)是(shi)導致處(chu)(chu)于負壓(ya)的(de)(de)空(kong)氣(qi)處(chu)(chu)理室漏風(feng)(feng)(feng)。在夏季,這會使(shi)未經處(chu)(chu)理的(de)(de)熱濕空(kong)氣(qi)進入送(song)(song)風(feng)(feng)(feng)系統,使(shi)機器露點不能(neng)滿(man)足(zu)設(she)計要求,送(song)(song)風(feng)(feng)(feng)溫度參數也就無法得到保證。國家(jia)技術監督局發布(bu)的(de)(de)《組(zu)(zu)(zu)合式空(kong)調機組(zu)(zu)(zu)》(GB/T14294-08)制造規范中規定:“機組(zu)(zu)(zu)內(nei)靜 壓(ya)保持700Pa時(shi),機組(zu)(zu)(zu)漏風(feng)(feng)(feng)率不得大(da)于3%”。有(you)的(de)(de)生產廠家(jia)在空(kong)氣(qi)處(chu)(chu)理機組(zu)(zu)(zu)框(kuang)架上開有(you)燕尾(wei)型(xing)密(mi)封槽,并配上相應的(de)(de)橡膠密(mi)封條,在額定工(gong)況下(xia),可以保證漏風(feng)(feng)(feng)率小(xiao)于2%,滿(man)足(zu)規范要求。這不失為(wei)一種(zhong)解決(jue)機組(zu)(zu)(zu)漏風(feng)(feng)(feng)問(wen)題的(de)(de)好辦法。
3 表面冷卻器選型計算
表面(mian)冷(leng)卻器(qi)(qi)是組合(he)式(shi)空氣(qi)處(chu)(chu)(chu)理(li)機(ji)(ji)(ji)組的(de)(de)(de)核心部分,是空氣(qi)與冷(leng)媒進(jin)行(xing)(xing)熱交(jiao)換(huan)的(de)(de)(de)地方。通常(chang)的(de)(de)(de)表冷(leng)器(qi)(qi)盤管(guan)結構為(wei)(wei)(wei)鋁質翅(chi)片(pian)經脹管(guan)機(ji)(ji)(ji)與銅管(guan)脹接。銅管(guan)的(de)(de)(de)壁(bi)厚(hou)(hou)、鋁箔(bo)的(de)(de)(de)厚(hou)(hou)度隨廠(chang)家不(bu)同(tong)而略(lve)有差(cha)別(bie),一般銅管(guan)壁(bi)厚(hou)(hou)為(wei)(wei)(wei)0.2~0.6mm,直徑為(wei)(wei)(wei)7~16mm,鋁箔(bo)厚(hou)(hou)度為(wei)(wei)(wei)0.15~0.20mm。值得(de)注(zhu)意的(de)(de)(de)是不(bu)同(tong)廠(chang)家在進(jin)行(xing)(xing)表冷(leng)器(qi)(qi)計算時(shi)選擇(ze)的(de)(de)(de)翅(chi)片(pian)間(jian)距有較大(da)(da)的(de)(de)(de)差(cha)別(bie)。以某系(xi)統為(wei)(wei)(wei)例(li)(li),處(chu)(chu)(chu)理(li)風(feng)量(liang)為(wei)(wei)(wei)79 000m3/h,冷(leng)量(liang)831kW,甲(jia)廠(chang)采(cai)(cai)(cai)(cai)用(yong)(yong)的(de)(de)(de)方案為(wei)(wei)(wei)降低表冷(leng)器(qi)(qi)翅(chi)片(pian)間(jian)距(約1.8mm),加大(da)(da)換(huan)熱面(mian)積;乙廠(chang)采(cai)(cai)(cai)(cai)用(yong)(yong)的(de)(de)(de)方案為(wei)(wei)(wei)選取常(chang)規翅(chi)片(pian)間(jian)距(約2.5mm),采(cai)(cai)(cai)(cai)用(yong)(yong)兩級表冷(leng)段串聯形式(shi),延長(chang)換(huan)熱時(shi)間(jian)。兩種(zhong)方案在風(feng)機(ji)(ji)(ji)功(gong)(gong)耗(hao)、水(shui)阻(zu)、斷(duan)面(mian)尺寸等方面(mian)都有各自(zi)的(de)(de)(de)優缺點(dian)。前者可(ke)能(neng)(neng)造成風(feng)阻(zu)較大(da)(da)從而加大(da)(da)風(feng)機(ji)(ji)(ji)功(gong)(gong)耗(hao),后(hou)者可(ke)能(neng)(neng)會加大(da)(da)機(ji)(ji)(ji)組尺寸和水(shui)流(liu)阻(zu)力。經過全面(mian)的(de)(de)(de)技術比較并綜合(he)考(kao)慮造價(jia)因素后(hou)決定采(cai)(cai)(cai)(cai)用(yong)(yong)乙廠(chang)產品。此(ci)例(li)(li)說明(ming)表冷(leng)器(qi)(qi)選型計算的(de)(de)(de)合(he)理(li)性事(shi)關整個空氣(qi)處(chu)(chu)(chu)理(li)機(ji)(ji)(ji)組的(de)(de)(de)使用(yong)(yong)性能(neng)(neng)及綜合(he)造價(jia),應引起足夠(gou)重視。
4風機的選型
風(feng)(feng)(feng)機(ji)是空氣(qi)處理(li)機(ji)組(zu)各功能段中唯一的耗能部分(fen)。與(yu)一般的風(feng)(feng)(feng)機(ji)相同,在(zai)定貨時應根據風(feng)(feng)(feng)量與(yu)壓頭的關(guan)系選擇(ze)合適的風(feng)(feng)(feng)機(ji)類(lei)型,如(ru)前向多翼或后(hou)彎(wan)式葉片(pian),以確保風(feng)(feng)(feng)機(ji)噪音及效率等指標達到最佳狀態。近些年從(cong)國(guo)外引進的機(ji)翼式風(feng)(feng)(feng)機(ji)具(ju)有較高的效率。
隨著(zhu)計算機技術的(de)(de)(de)發展和自動控制(zhi)水(shui)平的(de)(de)(de)提高,變風(feng)量(liang)(liang)系統(tong)越(yue)來越(yue)廣泛(fan)地應用在寫字樓、潔凈廠(chang)房(fang)、醫院等場合,因而對空調(diao)機組中送(song)、回風(feng)機的(de)(de)(de)選型(xing)提出了新的(de)(de)(de)更高要求。首先,風(feng)機的(de)(de)(de)特(te)(te)性曲(qu)線應具有平緩的(de)(de)(de)特(te)(te)征,這(zhe)樣(yang)當風(feng)量(liang)(liang)減(jian)少時可以使(shi)系統(tong)避免增加不(bu)必要的(de)(de)(de)靜(jing)壓;其次,選擇風(feng)機時其工作范圍應處于較穩(wen)定的(de)(de)(de)高效區(qu)內;第三(san),回/排風(feng)機應該(gai)與(yu)送(song)風(feng)機的(de)(de)(de)型(xing)號(hao)相同或為同一類型(xing),并具有相同或類似的(de)(de)(de)性能特(te)(te)征,這(zhe)樣(yang)方(fang)能保證運行時整個系統(tong)的(de)(de)(de)有效匹配。
5過濾器的選擇
過濾(lv)器(qi)分為:初效(xiao)過濾(lv)器(qi)(通(tong)常稱之為G級(ji)),中效(xiao)過濾(lv)器(qi)(通(tong)常稱之為F級(ji)),高效(xiao)過濾(lv)器(qi)
初效(xiao)過濾(lv)器分(fen)為:G1\ G2\ G3 \G4(G4為初過濾(lv)器過濾(lv)效(xiao)果最高,其他(ta)依次排列)
中(zhong)效(xiao)過濾器分為(wei):F5\ F6\ F7\F8\(F8為(wei)中(zhong)效(xiao)過濾器過濾效(xiao)果最高,其(qi)他依次(ci)排列)
高(gao)(gao)效過(guo)濾(lv)器分為:30萬級(ji)過(guo)濾(lv)\ 10萬級(ji)過(guo)濾(lv)\ 百級(ji)過(guo)濾(lv)(百級(ji)別過(guo)濾(lv)為高(gao)(gao)效過(guo)濾(lv)效果最高(gao)(gao),其(qi)他依次排列)
市場中主流過(guo)(guo)濾(lv)(lv)器(qi)(qi)為:無紡布過(guo)(guo)濾(lv)(lv)器(qi)(qi)\帶式過(guo)(guo)濾(lv)(lv)器(qi)(qi)\金屬過(guo)(guo)濾(lv)(lv)器(qi)(qi)\紙質過(guo)(guo)濾(lv)(lv)器(qi)(qi)\尼(ni)龍網過(guo)(guo)濾(lv)(lv)器(qi)(qi)\玻璃纖維過(guo)(guo)濾(lv)(lv)器(qi)(qi)\3M過(guo)(guo)濾(lv)(lv)器(qi)(qi)(近年(nian)來3M公司推出的一款(kuan)低阻力、高效率(lv)節能過(guo)(guo)濾(lv)(lv)器(qi)(qi)).
空(kong)氣(qi)(qi)中灰塵對人體(ti)健(jian)康和產品質量都(dou)有影響(xiang),尤其(qi)是(shi)一些(xie)特殊行(xing)業,如精(jing)密儀器、電(dian)子(zi)、制藥工業、醫院(yuan)等對空(kong)氣(qi)(qi)潔凈度要求(qiu)極高。這(zhe)就要求(qiu)根據不同行(xing)業的要求(qiu)選用組合式空(kong)氣(qi)(qi)處理機組。
用于舒(shu)適性空調環境的空氣(qi)對(dui)含(han)(han)塵量有一定的要(yao)求(qiu)(qiu)。一般規定室內(nei)含(han)(han)塵濃(nong)(nong)度(du)(du)為(wei)0.15~0.25mg/m3,并應(ying)濾(lv)(lv)掉≥10μm的塵粒(li)。這類空氣(qi)處理(li)機組(zu)的過(guo)濾(lv)(lv)段僅需(xu)配(pei)置(zhi)(zhi)粗效(xiao)及中效(xiao)過(guo)濾(lv)(lv)器(qi)即可。而對(dui)于上述的特殊行(xing)業還需(xu)配(pei)置(zhi)(zhi)高效(xiao)過(guo)濾(lv)(lv)器(qi)以(yi)達(da)到超(chao)凈凈化(hua),這類凈化(hua)要(yao)求(qiu)(qiu)甚高,室內(nei)空氣(qi)含(han)(han)塵濃(nong)(nong)度(du)(du)均以(yi)顆粒(li)計(ji)數濃(nong)(nong)度(du)(du)(粒(li)/L)表示。
6檢修方便
如上所述,組合式空氣處(chu)理(li)機組多用在系統風量較大的場合(通(tong)常在10 000m3/h以(yi)(yi)上),因此(ci)其外(wai)形(xing)尺寸往往較大。在現代建(jian)筑(zhu)中,由(you)于(yu)開(kai)發商(shang)或(huo)業主方投資及功能等原(yuan)因所限,機房(fang)尺寸常常被壓(ya)縮得很(hen)小(xiao),這樣就容易(yi)造成(cheng)表(biao)冷器(qi)(qi)、過濾(lv)器(qi)(qi)等需(xu)日常維護清洗的部件(jian)由(you)于(yu)空間(jian)太小(xiao)而無(wu)法(fa)抽出(chu)或(huo)者是很(hen)難抽出(chu)。有些建(jian)筑(zhu)建(jian)成(cheng)后原(yuan)先預留(liu)(liu)的設備(bei)(bei)檢(jian)修(xiu)通(tong)道被占(zhan)用,設備(bei)(bei)需(xu)更換(huan)或(huo)維修(xiu)時無(wu)法(fa)通(tong)行。所以(yi)(yi)在建(jian)設中,一方面(mian)(mian)要(yao)注意盡(jin)可能地預留(liu)(liu)檢(jian)修(xiu)空間(jian)及通(tong)道;另一方面(mian)(mian)在設備(bei)(bei)選型定貨時可以(yi)(yi)要(yao)求廠(chang)家根據機房(fang)實際(ji)情況改進空氣處(chu)理(li)機組自身結構,如表(biao)冷器(qi)(qi)設計成(cheng)兩側(ce)拔管等。 [1]